Series 6000
Enviromental and Mechanical Specifications
logo for Thytec Australia Pty Ltd

Series 6000 - Specifications

Series 6000 - Enviromental and Mechanical Specifications
Temperature Range: 0 - 40°C
Relative Humidity: 0 - 95% non condensing
Altitude: 2000 metres
Audible Noise: 58 dBA at 1 metre
Enclosure: Sheetmetal to IP30 (Lockable door)
Colour: Dove grey sides, Charcoal front panel (side panels removable). Other colours upon request.
Cable Entry: Front bottom
Service Access: Front
Ventilation: Forced draft cooling with air expelled to the top of the cabinet.
Model
Rating
kVA     kW
AC-DC Efficiency
Width
mm
Depth
mm
Height
mm
Weight kgs
UPS only
Internal Battery Time
6103
10               8
86%
820
610
1520
280
20-25 mins
6153
15             12
88%
820
610
1520
320
15 mins
6203
20             16
88%
820
610
1520
330
10 mins
6253
25             20
88%
820
610
1520
340
7 mins
6303
30             24
89%
820
610
1520
350
5 mins
6353
35             28
91%
820
610
1520
420
External
6403
40             32
91%
820
610
1520
450
External
6503
50             40
91%
820
610
1520
550
External
6603
60             48
91%
820
610
1520
600
External
6803
80             64
91%
1000
760
1520
700
External
61003
100           80
91%
1000
760
1520
850
External
NOTES:
1. Internal battery weight has not been allowed for in the UPS cabinet weight
2. Calculations at 0.7 P.F for back up time
3. Based on 12V 13 AH battery