| Model | 111 | SA8051 | SA8071 | SA8101 |
| Input Bypass |
Voltage Frequency Phase |
175-265 VAC 50/60Hz+ 5% Single Phase |
175-265 VAC 50/60Hz+ 5% Single Phase |
175-265 VAC 50/60Hz+ 5% Single Phase |
| Output | Voltage Capacity Wave Form Regulation Frequency THD Crest Factor |
220/230/240V 5kVA, 3.5kW Sinewave + 1% 50/60Hz+ 1% 3% 100% Linear Load 3:1 |
220/230/240V 7.5kVA, 5.2kW Sinewave + 1% 50/60Hz+ 1% 3% 100% Linear Load 3:1 |
220/230/240V 10kVA, 7kW Sinewave + 1% 50/60Hz+ 1% 3% 100% Linear Load 3:1 |
| Protection | Overload | Over 125% a delay 20 seconds, switch to bypass (all models this page) | ||
| Short Circuit Battery Low System Fault |
Yes Yes Yes |
Yes Yes Yes |
Yes Yes Yes |
|
| Alarm | AC Failure Overload Battery Low System Fault |
Yes Yes Yes Yes |
Yes Yes Yes Yes |
Yes Yes Yes Yes |
| Display | AC Input Fail | Red for AC Failure/Green for AC Normal (all models this page) | ||
| Fault | Red | Red | Red | |
| Overload | Red for AC Overload/Green for Normal (all models this page) | |||
| Inverter | Green | Green | Green | |
| Bypass | Yellow | Yellow | Yellow | |
| Battery Voltage | Voltage | 42-60VDC | 42-60VDC | 42-60VDC |
| Typical Efficiency | DC to AC | 85% | 85% | 85% |
| Cooling Fan | Yes | Yes | Yes | |
| Remote alarms | Voltage free contacts 1 NO and 1 NC | |||
| Contacts | DB 25 connector
for the following: Input AC Fail, Battery Low, Overload, Output Inverter Fail ( all models this page) |
|||
| Environment | Dimensions(mm) Net Weight |
610 W x 840 H x 820 D 105kg |
610 W x 84 0H x 820 D 140kg |
610 W x 1140 H x 820 D 195kg |
| Physical |
Temperature Humidity |
0 to 40°C Maximum 20 to 90% Non-condensing |
0 to 40°C Maximum 20 to 90% Non-condensing |
0 to 40°C Maximum 20 to 90% Non-condensing |
| Colour | Dove grey sides, Charcoal Front and back (all models this page) | |||
| Above specifications subject to change without notice. | ||||